Wire Size Calculator

Estimate a copper or aluminum AWG candidate from voltage, current, one-way distance and a voltage-drop target. Enter your measurements below and the estimate updates instantly.

Voltage-drop sizing only: this result does not check ampacity, breaker size, terminals or NEC/local approval.

Formula, validation and worked example reviewed November 12, 2026. See our calculation methodology.

US unitsFREE access0 signup
ELECTRICAL

Wire Size

US UNITS
Presets:

Enter line-to-line voltage and line current for balanced three phase. This fixed 75°C resistance model omits reactance and power-factor effects.

YOUR ESTIMATE
8 AWG copperAbout 1.95% voltage drop

Smallest listed size meeting this voltage-drop limit; not final wire sizing.

Required area 10,750 cmil · Listed selection 16,510 cmil · Listed range 14 AWG–4/0.

Fixed resistance model at 75°C: K = 12.9 copper / 21.2 aluminum Ω·cmil/ft. No temperature correction.

One-way length; AC assumes unity power factor and neglects reactance. Three phase assumes balanced load, line current and line-to-line voltage.

✓ Instant calculation on your device · Verify code-sensitive work locally

Sizing method and safety

Size by voltage drop, then verify everything else.

This wire gauge size calculator finds the circular-mil area needed for the selected voltage-drop limit, then moves up to the next conductor size in its limited common-size 14 AWG through 4/0 list, including 3 AWG. It is not a list of every AWG size.

How do you calculate wire size?

The size of an electrical conductor refers to its cross-sectional area (measured in circular mils (CM) or AWG in the US). The larger the cross-sectional area, the more current the wire can transmit with lower resistance—very similar to water flowing through a wider pipe with less pressure loss. We derive the required conductor area from Ohm's law and conductor resistivity:

V=I · R
(Ohm's law)
CM=2 · K · I · LVdrop
(Single-phase / DC)

where:

  • V_drop – Voltage drop calculated between the supply source and the farthest end of the wire, measured in volts (V_drop = V_source × (% drop ÷ 100));
  • I – Maximum current running through the conductor, measured in amps (convert power using the watts to amps calculator);
  • K – Specific resistance constant of the conductor material at 75°C (12.9 Ω·CM/ft for copper and 21.2 Ω·CM/ft for aluminum);
  • L – One-way length of the wire run from panel to load, measured in feet; and
  • CM – Cross-sectional area of the conductor, measured in circular mils (where 1,000 CM = 1 kcmil).

Calculating wire sizes for three-phase AC

For a balanced three-phase AC circuit, three current-carrying phase conductors are used instead of a two-wire loop. The calculator accepts line-to-line voltage and line current, modifying the required area of a single conductor to:

CM=√3 · K · I · LVdrop
(Three-phase AC)

The factor of √3 ≈ 1.732 converts between phase and line quantities in a balanced three-phase system, replacing the factor of 2. The calculator automatically selects the next AWG size up from its listed 14 AWG – 4/0 table so the voltage-drop limit is never exceeded. To check apparent power feeding that circuit, use the kVA to amps calculator.

The formula

How the result is calculated

  1. 01Allowed volts = system voltage x maximum drop percent / 100
  2. 02Required CM = phase multiplier x K x current x one-way length / allowed volts
  3. 03Select the next listed conductor with at least the required circular-mil area
Worked example

240 V, 30 A, 100 ft, 3% limit, copper

  1. Allowed drop is 240 x 3% = 7.2 V.
  2. Required area is 2 x 12.9 x 30 x 100 / 7.2 = 10,750 circular mils.
  3. 10 AWG is 10,380 CM, so the tool moves up to 8 AWG at 16,510 CM.
Voltage-drop result: 8 AWG copper, with an estimated 1.95% drop.
Quick reference chart

AWG Circular Mils & NEC Table 310.16 Base Ampacity Reference (14 AWG – 4/0)

Shows circular-mil area alongside base NEC Table 310.16 (60°C & 75°C) ratings and 240.4(D) small-conductor limits. Always verify both ampacity and voltage drop.

Wire SizeCircular Mils (CM)Copper 60°C / 75°C RefAluminum 60°C / 75°C Ref
14 AWG4,110 CM15 A / 15 A*Not typically used
12 AWG6,530 CM20 A / 20 A*15 A / 15 A*
10 AWG10,380 CM30 A / 30 A*25 A / 25 A*
8 AWG16,510 CM40 A / 50 A35 A / 40 A
6 AWG26,240 CM55 A / 65 A40 A / 50 A
4 AWG41,740 CM70 A / 85 A55 A / 65 A
2 AWG66,360 CM95 A / 115 A75 A / 90 A
1/0 AWG105,600 CM125 A / 150 A100 A / 120 A
2/0 AWG133,100 CM145 A / 175 A115 A / 135 A
4/0 AWG211,600 CM195 A / 230 A150 A / 180 A
Before you rely on the result

Common mistakes to avoid

  • Using the result as an ampacity or breaker-size approval.
  • Entering round-trip length instead of one-way distance.
  • Choosing the wrong conductor material or circuit phase.
  • Ignoring multiple loads tapped at different points along the run.
  • Treating an above-4/0 warning as a final engineered selection.
Questions answered

Calculator FAQ

How do I calculate wire size for voltage drop?+

Enter system voltage, current, one-way distance, conductor material, phase and maximum drop. The tool calculates required circular mils and selects the next listed AWG size.

What size wire do I need for a 50 amp breaker?+

Under NEC Table 310.16 (75°C terminals), a 50-amp circuit requires 6 AWG copper wire or 4 AWG aluminum wire. If the run exceeds 100 feet at 240V, upsize to 4 AWG copper to limit voltage drop to under 3%.

What size wire do I need for a 100 amp subpanel?+

A 100-amp subpanel typically uses 3 AWG copper wire or 1 AWG aluminum wire for short runs. For distances over 100 feet, 1/0 or 2/0 aluminum wire is standard to control voltage drop.

What size wire do I need for a 30 amp breaker?+

Under NEC 240.4(D), a 30-amp circuit requires 10 AWG copper wire (or 8 AWG aluminum). For long runs exceeding 85 feet at 240V, upsize to 8 AWG copper to keep voltage drop under 3%.

Why can the recommended wire be larger than expected?+

A long run, high current, low system voltage, or tight drop limit increases the circular-mil area required.

Does this check NEC ampacity?+

No. It only sizes for the selected voltage-drop limit. Ampacity, derating, terminals, protection, and local code require separate verification.

Why does the tool choose the next larger AWG?+

If the calculated area falls between listed conductors, the smaller one cannot meet the selected drop limit under this formula.

Can I estimate aluminum conductors?+

Yes. Select aluminum so the calculation uses the material constant configured for aluminum.

What does Above 4/0 range mean?+

The calculated area exceeds the largest size in this tool. Use a professional design that can consider larger or parallel conductors and the complete installation.

Can I use this wire gauge calculator for 12 V, 24 V, 120 V and 240 V?+

Yes. Enter the actual system voltage, load current and one-way distance. Lower-voltage systems often need larger conductors to hold the same percentage-drop limit.

How is a 3-phase wire-size result calculated?+

The calculator uses the balanced three-phase square-root-of-three multiplier with line-to-line voltage, line current and one-way distance, then selects the next listed AWG area that meets the chosen drop limit.

Is AWG wire size the same as cable size?+

This US-facing calculator reports American Wire Gauge sizes from 14 AWG through 4/0. Metric cable sizing normally uses square millimeters and requires a separate conversion and code check.

Practical selection guide

AWG wire sizing for common US systems.

Use this electrical cable size calculator when voltage drop is the sizing question. It selects the next listed AWG conductor that meets the entered drop limit, but it does not replace an ampacity or code calculation.

12 V and 24 V DC

Low-voltage runs can lose a meaningful share of supply voltage over distance. Enter the real one-way length and current instead of choosing a gauge by habit.

120 V and 240 V single phase

Select DC / single phase, choose copper or aluminum, and set the maximum drop used for the estimate. Verify ampacity and protection separately.

Balanced three phase

Select three phase to use the square-root-of-three sizing formula. A complete commercial design may also need load balance, power factor and installation conditions.

Wire size by amps

Current is one voltage-drop input, but it does not establish ampacity by itself. Check load rules, ampacity, terminals and protection separately.

50 Amp wire size (subpanel / EV charger)

For a 50A 240V circuit (range or Level 2 EV charger), standard 75°C copper requires 6 AWG (or 4 AWG aluminum). Over 100 feet, step up to 4 AWG copper to keep voltage drop under 3%.

100 Amp subpanel wire size

A 100A 240V subpanel requires 3 AWG copper or 1 AWG aluminum at standard 75°C ratings. Over long distances (>100 ft), 1/0 or 2/0 aluminum is commonly used to prevent voltage loss.

30 Amp wire size (dryer / RV / AC)

A 30A 240V circuit requires 10 AWG copper under NEC 240.4(D). For long runs exceeding 85 feet, upsize to 8 AWG copper to stay within the recommended 3% drop limit.

AWG range

The result moves to the next listed common size from 14 AWG through 4/0. An above-range result is a warning to obtain a professional design, not a conductor recommendation.

Method references: Southwire Voltage Drop Calculator · Southwire Building Wire Selector guidance