The multiplier is different

The calculator uses two times one-way distance for DC or single-phase circuits and the square root of three times one-way distance for a balanced three-phase circuit. The three-phase input uses line-to-line system voltage and assumes a balanced load under the simplified resistance model.

Changing the selector is not a way to improve a result. It must match the actual circuit. An unbalanced system, motor, transformer, nonlinear load or circuit with meaningful reactance can require a more complete engineering method.

How do you calculate voltage drop?

Every metallic conductor has internal electrical resistance. As current flows through a run of copper or aluminum wire, part of the source voltage is lost as heat along the cable path. Using Ohm's law (V = I × R) and circular-mil resistivity at 75°C, the voltage lost across a two-wire circuit is:

VD=2 · K · I · LCM
(Single-phase / DC)
% Drop=VDVsource · 100%
(Percentage loss)

where:

  • VD – Total voltage drop between the supply panel and the load terminals, measured in volts (need a target gauge instead? Use the wire size calculator);
  • K – Conductor resistance constant at 75°C (K = 12.9 for copper and K = 21.2 for aluminum in Ω·CM/ft);
  • I – Load current flowing through the circuit in amps (estimate from wattage with our watts to amps calculator);
  • L – One-way wire distance in feet (the multiplier of 2 already accounts for the return conductor); and
  • CM – Conductor cross-sectional area in circular mils from NEC Chapter 9, Table 8.

Three-phase AC voltage drop equation

In a balanced three-phase system, the return currents cancel in phase opposition, so the round-trip factor of 2 is replaced by √3:

VD3Φ=√3 · K · I · LCM
(Balanced 3-phase)

Subtract VD from the source voltage (V_load = V_source − VD) to find the actual voltage delivered to the equipment terminals. Explore all related tools in our electrical calculators hub.

Formula comparison

Simplified resistance-based formulas used by the Calc for Trades tools. L is one-way distance, K is the material constant, I is current and CM is conductor area in circular mils.
CircuitSimplified volts-lost formulaVoltage inputLoad assumption
DC / single phaseVd = 2 × K × I × L ÷ CMSystem voltageSingle current path and return
Balanced three phaseVd = √3 × K × I × L ÷ CMLine-to-line voltageBalanced phase currents

Worked example: 480 V, 50 A, 200 ft, 6 AWG copper

Using the calculator's copper constant and 26,240 circular mils for 6 AWG, the simplified DC/single-phase result is about 9.83 V lost, or 2.05% of 480 V. With the balanced three-phase multiplier, the estimate is about 8.52 V, or 1.77%.

The difference comes from the circuit geometry in the formula. It does not prove that 6 AWG is suitable. Ampacity, continuous load, motor rules, terminals, correction factors, protection and the actual system still govern the installed conductor.

Inputs that deserve a second check

  1. 01

    Line-to-line voltage

    For this balanced three-phase model, enter the actual line-to-line system voltage.

  2. 02

    Line current

    Use the design current determined for the circuit, not total three-phase current added together.

  3. 03

    One-way length

    Enter source-to-load distance once; do not double it before entering the value.

  4. 04

    Load behavior

    Identify motors, starting current, power factor, harmonics and imbalance that the simple model omits.

  5. 05

    Conductor conditions

    Verify material, area, temperature, conductor count, terminals and installation method separately.

When to stop using the simplified result

  • The three-phase load is materially unbalanced.
  • Motor starting or equipment inrush is important to operation.
  • Power factor or conductor reactance materially affects the circuit.
  • Parallel conductors, transformers or multiple loads occur along the run.
  • The system voltage or phase configuration is uncertain.
  • The result will be used for construction, permitting or equipment procurement without professional review.