Voltage Drop Calculator

Calculate voltage drop, percent loss and load voltage for AC, DC and three-phase circuits. Enter your measurements below and the estimate updates instantly.

For a balanced three-phase circuit, choose that circuit phase below or load the 480 V worked example.

Formula, validation and worked example reviewed November 12, 2026. See our calculation methodology.

US unitsFREE access0 signup
ELECTRICAL

Voltage Drop

US UNITS
Presets:

Enter line-to-line voltage and line current for balanced three phase. This fixed 75°C resistance model omits reactance and power-factor effects.

YOUR ESTIMATE
7.46 V drop3.11% voltage loss

Estimated load voltage 232.5 V

Fixed resistance model at 75°C: K = 12.9 copper / 21.2 aluminum Ω·cmil/ft. No temperature correction.

One-way length; AC assumes unity power factor and neglects reactance. Three phase assumes balanced load, line current and line-to-line voltage.

✓ Instant calculation on your device · Verify code-sensitive work locally

Formula and safety

Understand the voltage reaching the load.

This simplified resistance model uses K = 12.9 for copper and 21.2 for aluminum at 75°C, in ohm-circular-mils per foot. AC assumes unity power factor and ignores reactance; balanced three phase uses line current and line-to-line voltage. It is not a complete conductor design.

How do you calculate voltage drop?

Every metallic conductor has internal electrical resistance. As current flows through a run of copper or aluminum wire, part of the source voltage is lost as heat along the cable path. Using Ohm's law (V = I × R) and circular-mil resistivity at 75°C, the voltage lost across a two-wire circuit is:

VD=2 · K · I · LCM
(Single-phase / DC)
% Drop=VDVsource · 100%
(Percentage loss)

where:

  • VD – Total voltage drop between the supply panel and the load terminals, measured in volts (need a target gauge instead? Use the wire size calculator);
  • K – Conductor resistance constant at 75°C (K = 12.9 for copper and K = 21.2 for aluminum in Ω·CM/ft);
  • I – Load current flowing through the circuit in amps (estimate from wattage with our watts to amps calculator);
  • L – One-way wire distance in feet (the multiplier of 2 already accounts for the return conductor); and
  • CM – Conductor cross-sectional area in circular mils from NEC Chapter 9, Table 8.

Three-phase AC voltage drop equation

In a balanced three-phase system, the return currents cancel in phase opposition, so the round-trip factor of 2 is replaced by √3:

VD3Φ=√3 · K · I · LCM
(Balanced 3-phase)

Subtract VD from the source voltage (V_load = V_source − VD) to find the actual voltage delivered to the equipment terminals. Explore all related tools in our electrical calculators hub.

The formula

How the result is calculated

  1. 01DC / single phase: VD = 2 x K x I x L / CM
  2. 02Balanced three phase: VD = square root of 3 x K x I x L / CM
  3. 03Voltage loss percent = VD / system voltage x 100
Worked example

240 V, 30 A, 100 ft, 10 AWG copper

  1. Use 100 ft as the one-way length.
  2. 10 AWG has an area of 10,380 circular mils in this calculator.
  3. 2 x 12.9 x 30 x 100 / 10,380 = 7.46 V.
Estimated drop: 7.46 V, or 3.11%, leaving about 232.5 V at the load.
Quick reference chart

Copper vs. Aluminum Voltage Drop Reference (240V, 30A, 100 ft One-Way, 1Φ)

Calculated at 75°C (K = 12.9 Cu, 21.2 Al) alongside NEC Table 310.16 75°C copper ampacity reference.

Wire Gauge (AWG)Circular Mils (CM)Copper Drop (240V/30A/100ft)Aluminum Drop (240V/30A/100ft)
12 AWG6,530 CM11.85 V (4.94%)19.48 V (8.12%)
10 AWG10,380 CM7.46 V (3.11%)12.25 V (5.11%)
8 AWG16,510 CM4.69 V (1.95%)7.70 V (3.21%)
6 AWG26,240 CM2.95 V (1.23%)4.85 V (2.02%)
4 AWG41,740 CM1.85 V (0.77%)3.05 V (1.27%)
2 AWG66,360 CM1.17 V (0.49%)1.92 V (0.80%)
Before you rely on the result

Common mistakes to avoid

  • Entering round-trip distance when the formula already includes the return path.
  • Choosing single phase for a balanced three-phase circuit, or the reverse.
  • Selecting copper while the installed conductor is aluminum.
  • Treating low voltage drop as proof that conductor ampacity is adequate.
  • Ignoring motor starting current, temperature, terminals, routing, or loads at multiple points.
Questions answered

Calculator FAQ

How do I calculate voltage drop for a wire run?+

Use current, one-way distance, conductor material and circular-mil area with the circuit's phase multiplier, then divide the result by system voltage to find percent loss.

Does this voltage drop calculator match Southwire calculations?+

Yes. It uses the standard Ohm's law circular-mil resistance formula with industry-standard 75°C constants (K = 12.9 for copper, K = 21.2 for aluminum), matching Southwire and Mike Holt engineering formulas for unity power factor.

Should I enter one-way or round-trip distance?+

Enter the one-way conductor length. The DC / single-phase formula already applies a factor of two.

Is voltage drop the same as ampacity?+

No. Voltage drop estimates delivered voltage; ampacity concerns safe current-carrying capacity. Both must be checked separately.

What voltage-drop percentage is acceptable?+

That depends on the equipment, design, installation, and applicable code. This tool does not declare a circuit code-compliant.

Why is the three-phase formula different?+

A balanced three-phase calculation uses a square-root-of-three multiplier instead of the single-phase factor of two.

How do I use this as a 3-phase voltage drop calculator?+

Select three phase, enter line-to-line voltage, line current and the one-way conductor length. The tool applies the square-root-of-three multiplier for a simplified balanced circuit.

Can this calculator choose my breaker or final wire size?+

No. It does not check overcurrent protection, conductor ampacity, derating, terminal limits, conduit fill, or local requirements.

What is the single-phase voltage-drop formula?+

For the simplified resistance method used here, single-phase voltage drop is 2 x K x current x one-way length divided by conductor circular-mil area.

Practical selection guide

3-phase and single-phase voltage drop calculator methods.

Choose the circuit type before relying on the result. The 3-phase voltage drop calculator method uses line-to-line voltage and the square-root-of-three multiplier; DC and single phase use the two-conductor path.

Single phase / DC

Enter one-way distance. The calculator applies the return-path factor of two and reports volts lost, percent loss and estimated load voltage.

3-phase voltage drop

Select three phase and use line-to-line voltage, line current and one-way distance. Unbalanced loads and reactive effects need a fuller design method.

Copper or aluminum

Select the installed conductor material. Its configured K value changes the resistance estimate and therefore the calculated voltage loss.

Southwire formula comparison

Matches standard industry calculations: VD = (2 × K × I × L) ÷ CM for single-phase and (√3 × K × I × L) ÷ CM for three-phase using 75°C conductor resistivity constants.

Maximum circuit length target

NEC guidelines (Informational Note 210.19(A)) recommend keeping branch circuit drop under 3% and total feeder + branch circuit drop under 5%.

Method references: Mike Holt voltage-drop formulas and 75°C constants · Southwire Voltage Drop Calculator