Different questions, same conductor

How do you calculate wire size?

The size of an electrical conductor refers to its cross-sectional area (measured in circular mils (CM) or AWG in the US). The larger the cross-sectional area, the more current the wire can transmit with lower resistance—very similar to water flowing through a wider pipe with less pressure loss. We derive the required conductor area from Ohm's law and conductor resistivity:

V=I · R
(Ohm's law)
CM=2 · K · I · LVdrop
(Single-phase / DC)

where:

  • V_drop – Voltage drop calculated between the supply source and the farthest end of the wire, measured in volts (V_drop = V_source × (% drop ÷ 100));
  • I – Maximum current running through the conductor, measured in amps (convert power using the watts to amps calculator);
  • K – Specific resistance constant of the conductor material at 75°C (12.9 Ω·CM/ft for copper and 21.2 Ω·CM/ft for aluminum);
  • L – One-way length of the wire run from panel to load, measured in feet; and
  • CM – Cross-sectional area of the conductor, measured in circular mils (where 1,000 CM = 1 kcmil).

Calculating wire sizes for three-phase AC

For a balanced three-phase AC circuit, three current-carrying phase conductors are used instead of a two-wire loop. The calculator accepts line-to-line voltage and line current, modifying the required area of a single conductor to:

CM=√3 · K · I · LVdrop
(Three-phase AC)

The factor of √3 ≈ 1.732 converts between phase and line quantities in a balanced three-phase system, replacing the factor of 2. The calculator automatically selects the next AWG size up from its listed 14 AWG – 4/0 table so the voltage-drop limit is never exceeded. To check apparent power feeding that circuit, use the kVA to amps calculator.

Conceptual comparison. The ampacity result depends on all cited table conditions and other applicable rules.
CheckPrimary questionKey inputsTypical failure
AmpacityCan the conductor carry the load under its conditions of use?Material, insulation, terminals, ambient, conductor countExcess heating
Voltage dropHow much voltage is estimated to reach the load?Voltage, current, distance, material, phase, areaLow delivered voltage or poor operation

Worked example: a result near the boundary

For 240 V, 30 A, 100 ft one-way copper at a 3% target, 10 AWG produces about 3.11% in the site's simplified voltage-drop model. The calculator therefore moves to 8 AWG.

A table ampacity value viewed without terminal, load and installation context cannot reverse that voltage-drop observation. Likewise, selecting 8 AWG for drop does not prove its ampacity or protection is correct.

Recommended order of work

  1. 01

    Determine the design load

    Establish the current using the applicable equipment and load rules.

  2. 02

    Establish minimum ampacity

    Apply material, insulation, temperature, terminal, ambient and grouping conditions.

  3. 03

    Check voltage drop

    Use the actual voltage, distance, phase and material.

  4. 04

    Choose the controlling size

    Use a conductor that satisfies all applicable checks, then verify physical installation.

Warning signs

  • A calculator result is being called an NEC-approved size
  • Breaker rating is used as the only load input
  • Long distance is ignored after an ampacity lookup
  • The 90°C column is used without checking terminals
  • Adjustment factors are mentioned but not calculated