Aluminum AWG comparison

How do you calculate voltage drop?

Every metallic conductor has internal electrical resistance. As current flows through a run of copper or aluminum wire, part of the source voltage is lost as heat along the cable path. Using Ohm's law (V = I × R) and circular-mil resistivity at 75°C, the voltage lost across a two-wire circuit is:

VD=2 · K · I · LCM
(Single-phase / DC)
% Drop=VDVsource · 100%
(Percentage loss)

where:

  • VD – Total voltage drop between the supply panel and the load terminals, measured in volts (need a target gauge instead? Use the wire size calculator);
  • K – Conductor resistance constant at 75°C (K = 12.9 for copper and K = 21.2 for aluminum in Ω·CM/ft);
  • I – Load current flowing through the circuit in amps (estimate from wattage with our watts to amps calculator);
  • L – One-way wire distance in feet (the multiplier of 2 already accounts for the return conductor); and
  • CM – Conductor cross-sectional area in circular mils from NEC Chapter 9, Table 8.

Three-phase AC voltage drop equation

In a balanced three-phase system, the return currents cancel in phase opposition, so the round-trip factor of 2 is replaced by √3:

VD3Φ=√3 · K · I · LCM
(Balanced 3-phase)

Subtract VD from the source voltage (V_load = V_source − VD) to find the actual voltage delivered to the equipment terminals. Explore all related tools in our electrical calculators hub.

240 V, 30 A, 100 ft one-way, simplified DC/single-phase model using K = 21.2.
Aluminum AWGEstimated volts lostEstimated percentage
1430.95 V12.90%
1219.48 V8.12%
1012.25 V5.11%
87.70 V3.21%
64.85 V2.02%
43.05 V1.27%
21.92 V0.80%

Do not convert material by a fixed AWG rule

A statement such as 'move up two sizes' hides the actual load, distance, target, ampacity column and terminal conditions. Recalculate area and then verify the complete system.

A larger aluminum conductor can affect lug range, enclosure bending space, raceway fill and pulling. Compare installed-system requirements rather than price per foot alone.

Termination checklist

  1. 01

    Read equipment markings

    Confirm every lug and connector is identified for aluminum and the selected size.

  2. 02

    Follow preparation instructions

    Use the manufacturer-specified stripping, cleaning, compound and torque procedures.

  3. 03

    Check physical fit

    Verify raceway, bending space and enclosure capacity for the actual product.

  4. 04

    Document material

    Save the conductor alloy, insulation, AWG and termination products with the calculation.

What the chart does not show

  • Permitted ampacity
  • Terminal compatibility
  • Conduit fill
  • Parallel conductor rules
  • Local inspection requirements
  • Manufacturer-specific resistance and dimensions